Verkada AC62 door controller
Sixteen-door controller for larger buildings and campuses, with a fire alarm interface and an optional 18Ah battery.
AC62 at a glance
| AC62 | |
|---|---|
| Model and variants | AC62-HW |
| Doors / readers | Up to 16 doors; 1 Verkada/RS-485 and 1 Wiegand port per door, plus 2 AUX reader ports (RS-485); each reader <250mA, up to 16 powered at once |
| Inputs | Per door: 2x REX + 1x DPI (dry); plus 2x AUX dry inputs |
| Outputs | 1 wet or dry relay per door (wet 12V 1A or 24V 0.5A; dry 24VDC @ 2A); 2x AUX dry relays; AUX power 2x 12V 1A and 2x 24V 0.5A |
| Fire alarm interface | FAI removes power from maglocks on fire alarm |
| Power | 100-240VAC 50-60Hz; 350W max |
| Battery backup | Optional ACC-BAT-18AH (24V, 18Ah sealed lead acid) |
| Network | Ethernet 100/1000 Mbps RJ-45; USB 2.0 |
| Mounting | Wall mounting plate, 6x #12x1in screws; 773 x 499 x 186 mm, 20 kg |
| Operating temp | 0 to 50°C, 5-90% humidity |
| Licence | One door licence per door connected, up to sixteen. |
| Warranty | 10 years |
From Verkada’s datasheets: door controller ac62 datasheet (PDF), help centre. Checked 17 October 2026.
How we install the AC62
Door hardware, cabling, power and the fire alarm interface are all done by our own electricians, so one contractor is responsible for the door working. We set up doors, schedules and credentials in Command and train whoever manages them.
Other access control models: AC12, AC43, AX11, AD34, AD64, AF64. See all on Verkada access control or the model guide.
AC62 questions
What licence does the AC62 need?
Can you add a AC62 to my existing Verkada system?
Do you just supply the AC62, or install it too?
Need the AC62 on your site?
Free survey and a written design with an itemised quote. Call or send the form below.
Book a site survey Call 01727 822 833Tell us what you need
Send us a few details and one of our engineers — not a call centre — will come back to you within one working day.